3.3 Main Menu - Brakes - Group 2
2-00 DC Hold/Motor Preheat Current
Range: Function:
50.0 %* [0.0 -
160.0 %]
Set holding current as a percentage of the
rated motor current IM,N 1-24 Motor Current.
2-00 DC Hold/Motor Preheat Current holds the
motor function (holding torque) or pre-heats
the motor. This parameter is active if DC
hold is selected in 1-72 Start Function [0] or
1-80 Function at Stop [1].
NOTE
The maximum value depends on the rated motor current.
Avoid 100% current for too long. It may damage the motor.
2-01 DC Brake Current
Range: Function:
50.0 %* [0.0 - 150.0
%]
Set current as % of rated motor current,
1-24 Motor Current. DC brake current is
applied on stop command, when speed is
below the limit set in 2-04 DC Brake Cut In
Speed; when the DC Brake Inverse function
is active; or via the serial port. See 2-02 DC
Braking Time for duration.
50.0 %* [0.0 - 150.0
%]
NOTE
The maximum value depends on the rated motor current.
Avoid 100% current for too long. It may damage the motor.
2-02 DC Braking Time
Range: Function:
10.0 s* [0.0 - 60.0 s] Set the duration of the DC braking current
set in 2-01 DC Brake Current, once activated.
2-04 DC Brake Cut In Speed
Range: Function:
0.0 Hz* [0.0 - 400.0
Hz]
This parameter is for setting the DC brake
cut in speed at which the DC braking
current 2-01 DC Brake Current is to be
active, in connection with a stop
command.
3.3.1 2-1* Overvoltage Control
Par. group for selecting dynamic braking parameters.
2-10 Brake Function
Option: Function:
[0] Off No brake resistor installed.
2-17 Over-voltage Control
Option: Function:
Select whether to enable OVC, which reduces the
risk of drive trip due to over voltage on the DC link
caused by generative power from load.
[0] Disabled No OVC required.
[2] * Enabled Activates OVC.
NOTE
The ramp time is automatically adjusted to avoid tripping of
the frequency converter.
Parameters VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark 29
3
3