Danfoss VLT 2800 Manuel de service Page 66

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 95
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 65
VLT
®
2800 Series
Electrical installation, control cables Control cables must be screened/armoured. The
screen must be connected to the frequency converter
chassis by means of a clamp. Normally, the screen
must also be connected to the chassis of the
controlling unit (use the instructions for the unit in
question). In connection with very long control cables
and analogue signals, in rare cases depending on
the installation, 50/60 Hz earth loops may occur
because of noise transmitted from mains supply
cables. In this connection, it may be necessary
to break the screen and possibly insert a 100 nF
capacitor between the screen and the chassis.
MG.28.A9.02 - VLT is a registered Danfoss trademark
66