Danfoss VLT 2800 Manuel d'utilisateur Page 2

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 1
195R0033
Parameter- Selection/range Factory Setting
# description setting
132 DC brake 0-100% of max. DC brake voltage 0%
voltage
133 Start voltage 0.00-100.00 V Depends on unit
134
Load
0.00-300.0% 100,0%
compensation
135 U/f ratio 0.00-20.0 at Hz Depends on unit
136 Slip -500 - +500% of rated 100%
compensation slip compensation
137 DC 0-100% of max. DC hold voltage 0%
hold voltage
138 Brake cut 0.5 - 132.0/1000.0 Hz 3.0 Hz
out value
139 Brake cut 0.5 - 132.0/1000.0 Hz 3.0 Hz
in frequency
140 Current, minimum 0 - 100% of Within 0%
value
142 Spread 0.000-XXX.XXX Depends on
reactance choice of motor
143 Internal fan [0]=Automatic, [1]=Always switched [0] = Automatic
control on, [2]=Always switched off
144 Gain AC brake 1.0 - 1.50 1.30
146 Reset voltage [0]=Off [0]=Off
vector [1]=Reset
200 Output [0]=Only clockwise, 0-132 Hz [0]=Only clock-
frequency range [1]=Both directions, 0-132 Hz wise, 0-132 Hz
[2]=Only anti-clockwise, 0-132 Hz
[3]=Only clockwise, 0-1000 Hz
[4]=Both directions, 0-1000 Hz
[5]=Only anti-clockwise, 0-1000 Hz
201 Output frequency 0.0 - f
MAX
0.0 Hz
low limit, f
MIN
202 Output frequency f
MIN
- 132/1000 Hz 132 Hz
high limit, f
MAX
203 Reference/ [0]=Min. ref./fb - Max. ref./fb [0]=Min. ref./fb -
feedback range [1]=-Max. ref./fb - Max. ref./fb Max. ref./fb
204 Min. reference Par. 100 Config. = Open loop [0] 0.000 Hz
Ref
MIN
- 100,000.000 - par. 205 Ref
MAX
Par. 100 Config. = Closed loop [1]/[3] 0.000
- Par. 414 Min. fb - Par. 205 Ref
MAX
205 Max. reference Par. 100 Config. = Open loop [0] 50.000 Hz
Ref
MAX
Par. 204 Ref
MIN
-1000.000 Hz
Par. 100 Config. = Closed loop [1]/[3] 50.000
Par. 204 Ref
MIN
- Par. 415 Max. fb
206 Ramp type [0]=Linear [1]=Sine-shaped [0]=Linear
[2]=Sine-
2
shaped
207 Ramp-up time 1 0.02-3600 sec. 3.00 sec.
208 Ramp-down 0.02-3600 sec. 3.00 sec.
time 1
209 Ramp-up time 2 0.02-3600 sec. 3.00 sec.
210 Ramp-down 0.02-3600 sec. 3.00 sec.
time 2
211 Jog ramp time 0.02-3600 sec. 3.00 sec.
212 Quick stop 0.02-3600 sec. 3.00 sec.
ramp-down time
213 Jog frequency 0.0- Par. 202 Output frequency 10.0 Hz
high limit
214 Reference [0]=Sum [0]=Sum
function [1]=Relative
[2]=External/preset
215 Preset ref. 1 -100.00% - + 100.00% 0.00%
216 Preset ref. 2 -100.00% - + 100.00% 0.00%
217 Preset ref. 3 -100.00% - + 100.00% 0.00%
218 Preset ref. 4 -100.00% - + 100.00% 0.00%
219 Catch up/slow 0.00-100% of the current reference 0.00%
down reference
221 Current limit, [A] = x-xxx.x% of I
MAX
160%
I
LIM
223 Warning: 0.0 - Par. 224 Warning: High current, 0.0 A
Low current I
HIGH
224 Warning: Par. 223 Warning: Low current,I
MAX
High current I
LOW
- I
MAX
225 Warning: 0.0 - par. 226 Warning: High frequency, 0.0 Hz
Low frequency f
HIGH
226 Warning: Par 225 f
LOW
- 120/1000 Hz 132.0 Hz
High frequency
227 Warning: 100,000.000 - par. 228 -4000.000
Low feedback, Warning: FB
HIGH
FB
LOW
228 Warning: Par. 227 - Warning: 4000.000
High feedback, FB
LOW
- 100,000.000
FB
HIGH
229 Frequency bypass, 0 (OFF) - f
MAX
0 Hz
bandwidth
230
Frequency
0 -132/1000 Hz 0.0 Hz
bypass 1
231 Frequency 0 -132/1000 Hz 0.0 Hz
bypass 2
302 Digital input See manual [7]=Start
Terminal 18
303 Digital input See manual [9]=Reversing
Terminal 19
304 Digital input See manual [3]=Reset and
Terminal 27 coasting inverse
305 Digital input See manual [13]=Jog
Terminal 29
307 Digital input See manual [0]=No operation
Terminal 33
308 Term. 53, analo- [0]=No operation, [1]=Reference [1]=Reference
gue input voltage [2]=Feedback
309 Term. 53, Min. 0.00 - 10.0 V 0.0 V
scaling
310 Term. 53, Max. 0 - 10.0 V 10.0 V
scaling
314 Term. 60, analo- [0]=No operation, [1]=Reference [0]=No operation
gue input current [2]=Feedback
315 Term. 60, Min. 0.0 - 20.0 mA 0.0 mA
scaling
316 Term. 60, Max. 0.0 - 20.0 mA 20.0 mA
scaling
317 Time out 1 - 99 sec. 10 sec.
318 Function after [0]=No operation, [1]=Freeze output [0]=No operation
time out frequency, [2]=Stop, [3]=Jog,
[4]=Max. speed, [5]=Stop and trip
319 Term. 42, See manual [7] = 0-I
INV.
analogue output 0-20 mA
323 Relay output See manual [1]=Drive ready
327 Pulse/reference 150 - 67600 Hz 5000 Hz
feedback
341 Term. 46, See manual [1]=Drive ready
digital output
342 Term. 46, Max.
pulse output 150 - 10,000 Hz 5000 Hz
343 Precise stop See manual [0] = Normal
function ramp stop
344 Counter value 1 - 999999 100000 pulses
349 Speed comp 0 - 100 ms 10 ms
delay
400 Brake function [0]=Off, [1]=Resistor brake Depends on unit
[4] AC brake, [5]=Load sharing
405 Reset function See manual [0]=Manual reset
406 Automatic 0 - 10 sec. 5 sec.
restart time
409 Trip delay 0 - 60 sec. (61=OFF) OFF
overcurrent
411 Switching 3000 - 14000 Hz 4500 Hz
frequency
412 Output frequency [2] = No LC-filter [2] = No LC-filter
dependent [3] = LC-filter fitted
switching
413 Overmodulation [0]=Off, [1]=On [1]=On
function
414 Min. feedback, -100,000.000 - par. 415 FB
MAX
0.000
FB
MIN
415 Max. feedback, par. 414 FB
MIN
- 100,000.000 1500.000
FB
MAX
416 Process units See manual [0]=No unit
417 Speed PID pro- 0.000 (OFF) - 1.000 0.010
portional gain
418 Speed PID 20.00 - 999.99 ms (1000 = OFF) 100.00 ms
integral time
419 Speed PID 0.00 (OFF) - 200.00 ms 20 ms
differential time
420 Speed PID 5.0 - 50.0 5.0
D-gain limit
421 Speed PID 20 - 500 ms 20 ms
lowpass filter time
423 U1 voltage 0.0 - 999.0 V par. 103
424 F1 frequency 0.0 - par. 426 F2 frequency par. 104
Motor frequency
425 U2 0voltage 0.0 - 999,0 V par. 103
426 F2 frequency Par. 424 F1 frequency - par. 104
par. 428 F3 frequency Motor frequency
427 U3 voltage 0.0 - 999.0 V 0.0 V
428 F3 frequency Par. 426 F2 frequency - 1000 Hz par. 104
Motor frequency
437 Process PID [0]=Normal, [1]=Inverse [0]=Normal
Normal/inverse
control
438 Process PID [0]=Not active, [1]=Active [1]=Active
anti windup
439 Process PID f
MIN
- f
MAX
(par. 201/202) Par. 201 Output
start frequency frequency low
limit, f
MIN
440 Process PID 0.0 - 10.00 0.01
proportional gain
441 Process PID 0.01 - 9999.99 ms (OFF) OFF
integration time
442 Process PID 0.00 (OFF) - 10.00 sec. 0.00 sec.
differentiation time
443 Process PID diff. 5.0 - 50.0 5.0
gain limit
444 Process PID 0.02 - 10.00 0.02
lowpass filter time
445 Flying start [0]=Off, [1]=OK same direction, [0]=OFF
[2]=OK both directions,
[3]=DC brake and start
451 FF factor 0 - 500% 100%
452 Controller 0 - 200% 10%
range
Parameter- Selection/range Factory Setting
# description setting
456 Brake voltage 0 - 25 V if 200V device 0
reduce 0 - 50 V if 400V device 0
Terminal Rail Layout
Electronic Power Solutions Pty Ltd | 3/42 Deakin St, Brendale 4500, Qld, Australia | www.electronicpowersolutions.com | 1300 797 655
Leaders in Electronic Motor Control
Vue de la page 1