Danfoss VLT 6000 HVAC Manuel de service Page 39

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 177
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 38
VLT
®
6000 HVAC
39MG.60.B1.02 - VLT is a registered Danfoss trademark
Introduction to
HVAC
LC filters 6002-6006, 200 - 240 V / 6002-6011 380 - 460 V
The drawing on the left gives the measurements of IP
20 LC filters for the above-mentioned power range.
Min. space above and under enclosure: 100 mm.
IP 20 LC filters have been designed for side-by-side
installation without any space between enclosures.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable
If EMC standards are to be complied with:
- EN 55011-1B: Max. 50 screened/armoured cable
Bookstyle: Max. 20 m screened/armoured cable
- EN 55011-1A: Max. 150 m screened/armoured cable
Weight: 175Z0825 7.5 kg
175Z0826 9.5 kg
175Z0832 9.5 kg
Installation of LC filter IP 20 Bookstyle
Installation of LC filter IP 20
LC filter
LC filter
VLT
VLT
Vue de la page 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 176 177

Commentaires sur ces manuels

Pas de commentaire