Danfoss VLT 8000 AQUA Instructions d'exploitation Page 59

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 210
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 58
VLT
®
8000 AQUA
Installation
Extra protection with regard to indirect contact
ELCB relays, multiple protective earthing or earthing can
be used as extra protection, provided that local safety
regulations are complied with. In the case of an earth
fault, a DC content may develop in the faulty current.
Never use ELCB relays, type A, since such relays
are not suitable for DC fault currents.
If ELCB relays are used, this must be:
Suitable for protecting equipment with a direct
current content (DC) in the faulty current
(3-phase bridge rectifier)
Suitable for power-up with short charging
current to earth
Suitable for a high leakage current
MG.83.A2.02 - VLT is a registered Danfoss trademark
57
Vue de la page 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 209 210

Commentaires sur ces manuels

Pas de commentaire