Page 1 - QQuick Guide

MAKING MODERN LIVING POSSIBLEQQuick GuideVLT® HVAC Basic Drivewww.danfoss.com/drives *MG18A302*132R0078 MG18A302 Rev. 2011-09-20

Page 2 - 1 Quick Guide

H6 FrameIP20 380-480 V 30-45 kWIP20 200-240 V 15-18.5 kWIP20 525-600 V 22-30 kW19599L1 91 / L2 92 / L3 93U 96 / V 97 / W 9803 02 0106 05 04234130BB762

Page 3

H8 FrameIP20 380-480 V 90 kWIP20 200-240 V 37-45 kWIP20 525-600 V 75-90 kW130BB764.1012349897969995939291L1L1L1UVw1 Line2 Relays3 Earth4 MotorH9 Frame

Page 4 - 1.2.4 Avoid Unintended Start

130BA263.1095MAINS+DCBR-BR+UVW919293L1L2L3RELAY 1 RELAY 2+DCBR-BR+UVWMAINSL1 L2 L391 92 93RELAY 1 RELAY 299- LC -130

Page 5 - 1.3 Installation

I2 FrameIP54 380-480 V 0.75-4.0 kW130BC299.10732518461 RS 4852 Line in3 Earth4 Wire clamps5 Motor6 UDC7 Relays8 I/OI3 FrameIP54 380-480 V 5.5-7.5 kW13

Page 6 - 1.3.3 Dimensions

IP54 I2-I3 frame130BC203.10I6 FrameIP54 380-480 V 22-37 kW130BT326.10130BT325.10Quick Guide VLT HVAC Basic Drive Quick GuideMG18A302 - VLT® is a regis

Page 7

311130BA215.10RELAY 1RELAY 299603 02 0190 05 04I7, I8 FrameIP54 380-480 V 45-55 kWIP54 380-480 V 75-90 kW91L192L293L396U97V98W88DC-89DC+81R-

Page 8

Circuit Breaker FuseUL Non UL UL Non UL BussmannBussmannBussmannBussmannMax fusePower kW Type RK5 Type RK1 Type J Type T Type G3 x 200 - 240

Page 9

Circuit Breaker FuseUL Non UL UL Non UL BussmannBussmannBussmannBussmannMax fusePower kW Type RK5 Type RK1 Type J Type T Type G3 x 525 - 600

Page 10 - U 96 / V 97 / W 98

L1L2L3PEMin. 16 mm2Equalizing cableControl cablesAll cable entries inone side of panelEarthing railCable insula-tion strippedOutput con-tactor etc.Mot

Page 11 - 130BA262.10

1.3.8 Control TerminalsIP20 200-240 V 0.25-11 kW and IP20 380-480 V 0.37-22 kW:130BB622.10Illustration 1.4 Location of Control Terminals1. Place a scr

Page 12 - 130BA725.10

Contents1 Quick Guide21.1 Safety21.1.1 Warnings 21.1.2 Safety Instructions 21.2 Introduction31.2.1 Available Literature 31.2.2 Approvals 31.2.3 IT Mai

Page 13 - IP54 380-480 V 0.75-4.0 kW

1.3.9 Electrical OverviewL1L2L33 PhasepowerinputPEPE+10Vdc0-10Vdc-0-10Vdc-50 (+10V OUT)54 (A IN)53 (A IN)55 (COM A IN/OUT)0/4-20 mA0/4-20 mA42 0/4-20m

Page 14 - 130BT325.10

1.4 Programming1.4.1 Programming with the Local ControlPanel (LCP)NOTEThe frequency converter can also be programmed from aPC via RS485 com-port by i

Page 15 - 130BA215.10

At power-upAt the first power-up the user is asked to choose preferredlanguage. Once selected this screen will never be shownagain in the following po

Page 16

Setup 1Setup 1 Setup 1 Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1Setup 1S

Page 17

The FC101 Start-up Wizard for Open Loop ApplicationsNo & Name Range Default Function0-03 Regional Settings [0] International[1] US0 0-06 Grid Typ

Page 18 - MG18A302 - VLT

No & Name Range Default Function3-03 Maximum Reference -4999-4999 50 The maximum reference is the lowest obtainableby summing all references5-40 F

Page 19 - 130BB624.10

Closed Loop Set-up Wizard6-29 Terminal 54 Mode[1] Voltage mode 6-25 Terminal 54 High Ref./Feedb. Value0050 Hz20-94 PI Integral Time9999 sCurrentVol

Page 20 - 1.3.9 Electrical Overview

Closed Loop Set-up WizardNo & Name Range Default Function0-03 Regional Settings [0] International[1] US0 0-06 Grid Type [0]-[[132] please seestar

Page 21 - Panel (LCP)

Motor Set-upThe Quick Menu Motor Set-up guides through the neededmotor parameters.No & Name Range Default Function0-03 RegionalSettings[0] Interna

Page 22 - Applications

1.5 Parameter OverviewParameter Overview0-** Operation / Display0-0* Basic Settings0-01 Language*[0] English[1] Deutsch[2] Francais[3] Dansk[4] Espan

Page 23 - 22 MG18A302 - VLT

1 Quick Guide1.1 Safety1.1.1 WarningsWARNINGHigh Voltage WarningThe voltage of the frequency converter is dangerouswhenever it is connected to mains.

Page 24

Parameter Overview1-63 Slip Compensation TimeConstant0.05 - 5.00 s, * 0.101-64 Resonance Dampening0 - 500%, * 1001-65 Resonance Dampening TimeConstant

Page 25

Parameter Overview[73] Logic rule 3[74] Logic rule 4[75] Logic rule 5[80] SL digital output A[81] SL digital output B[82] SL digital output C[83] SL d

Page 26 - Closed Loop Set-up Wizard

Parameter Overview*[0] Digital and ctrl.word[1] Digital only[2] Controlword only8-02 Control Source[0] None*[1] FC Port8-03 Control Timeout Time0.1 -

Page 27

Parameter Overview[29] Start timer 0[30] Start timer 1[31] Start timer 2[32] Set digital out A low[33] Set digital out B low[34] Set digital out C low

Page 28

Parameter Overview20-01 Feedback 1 Conversion*[0] Linear[1] Square root20-8* PI Basic Setting20-81 Process PI Normal/ InverseControl*[0] Normal[1] Inv

Page 29 - 1.5 Parameter Overview

FaultnumberAlarm/WarningBitNumber Fault text Warning AlarmTriplocked Cause of problem50 AMACalibrationfailed X Contact your local Danfoss supplie

Page 30

1.7 General Specifications1.7.1 Mains Supply 3 x 200-240 V ACfrequency converter PK25PK37PK75P1K5P2K2 P3K7P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45

Page 31

1.7.2 Mains Supply 3 x 380-480 V ACFrequency converter PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90KTypica

Page 32

Frequency converter PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90KEstimated power loss [W], Best case/typic

Page 33

1.7.3 Mains Supply 3 x 380-480 V ACFrequency converter PK75 P1K5 P2K2 P3K0 P4KO P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90KTypical sha

Page 34 - 1.6 Warnings and Alarms

1.2 Introduction1.2.1 Available LiteratureThis quick guide contains the basic information necessaryfor installing and running the frequency converter

Page 35

Frequency converter PK75 P1K5 PK2K2 PK3KO PK4KO PK5K5 PK7K5 PK11K PK15K P18K P22K P30K P37K P45K P55K P75K P90KEstimated power loss [W], Best case/typ

Page 36 - 1.7 General Specifications

1.7.4 Mains Supply 3 x 525-600 V ACFrequency converter P2K2 P3K0 P5K5 P7K5 P11K P15K P22K P30K P45K P55K P75K P90KTypical shaft output (kW) 2.2 3.0 5.

Page 37 - 130BB633.10

1.7.5 EMC Test ResultsThe following test results have been obtained using a system with a frequency converter, a screened control cable, a controlbox

Page 38

Protection and features•Electronic thermal motor protection against overload.•Temperature monitoring of the heatsink ensures that the frequency conver

Page 39

Analog inputsNumber of analog inputs 2Terminal number 53, 54Terminal 53 mode Parameter 6-19: 1 = voltage, 0 = currentTerminal 54 mode Parameter 6-29:

Page 40

All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) andother high-voltage terminals

Page 41

MAKING MODERN LIVING POSSIBLEQQuick GuideVLT® HVAC Basic Drivewww.danfoss.com/drives *MG18A302*132R0078 MG18A302 Rev. 2011-09-20

Page 42 - 1.7.5 EMC Test Results

1.2.5 Disposal InstructionEquipment containing electrical componentsmust not be disposed of together with domesticwaste.It must be separately collecte

Page 43 - 42 MG18A302 - VLT

1.3.3 DimensionsAabBC D130BB614.10efade130BC205.10efae130BC246.10Enclosure Power [kW] Height [mm] Width [mm] Depth[mm]Mounting hole [mm] Max.WeightFr

Page 44

Enclosure Clearance needed for free air passage [mm]Frame IP class Above unit Below unitH1 20 100 100H2 20 100 100H3 20 100 100H4 20 100 100H5 20 100

Page 45 - 44 MG18A302 - VLT

Power (kW) Torque (Nm)Frame IP class 3 x 525-600 V Line Motor DC connection ControlterminalsEarth RelayH9 IP20 2.2-7.5 1.8 1.8 notrecommended0.5 3 0.6

Page 46

1.3.5 Connecting to Mains and MotorThe frequency converter is designed to operate allstandard three-phased asynchronous motors. Formaximum cross-secti