Product Code No
Radiator
Connection
ISO 7-1
System
Connec-
tion
ISO 228-1
Kvs
Value
(m
3
/h)
1)
Max
operation
pressure
(bar)
Max.
diff.
pressure
(bar)
2)
Test
pressure
(bar)
Max.
water
temp
(°C)
Valve body with
angle piece
3)
013G336200
R ½
2.5
10
0.6
16 120
Manifold valve
RA-KE
3)
013G336600
G ¾
Manifold valve
RA-KEW
3)
013G336800
Connection pipe
L650 x ø 15mm
L950 x ø 15mm
013G337800
013G337700
Set pack for floor
connection
013G334100 Valve body and manifold valve RA-KE
Set pack for wall
connection
013G334300 Valve body and manifold valve RA-KEW
1) Capacity of manifold assembly. Bypass through radiator: 35%.
2) The maximum differential pressure specified is the maximum pressure at which the valves give satisfactory
regulation. As with any device which imposes a pressure drop in the system, noise may occur under certain
flow/pressure conditions. To ensure quiet operation, maximum pressure drop should not exceed 30 to 35 kPa.
The differential pressure can be reduced by using Danfoss differential pressure regulators.
3) Includes compression fittings for connection pipe
RA-KEW
RA-KE
Versatile control units for all types of •
radiator
Standard ½” side connections•
Suitable for 1-pipe pumped systems•
Suitable for use with all RA2000 •
sensors
Range of compression fittings •
available
The manifold assemblies RA-KE and
RA-KEW are versatile control units for all
types of radiators with standard ½” side
connections. RA-KE and RA-KEW valves
are for 1-pipe pumped systems.
The manifold assembly includes a
manifold valve body with shut off
facility, a connection pipe and a radiator
valve body.
The centre distance between
connection pipe is 35mm, which allows
system pipes to be connected using a
junction box.
Danfoss manifold assemblies can be
used with all RA2000 sensors.
A wide range of compression fittings
for steel, copper, PEX and AluPex piping
allows fast and flexible installation. See
page 20.
To avoid deposits and corrosion the
water quality should comply to VDI
2035 guidelines
ManifoldAssembliesfor1-PipeSystems
RA-KE and RA-KEW
Manifoldassembliesusedin1-pipesystems