The grey
side of the
ECL Card
Basic set-up
The grey
side of the
ECL Card
Basic set-up
8
1
1
1
1
ON
2
ON
2
1 Limit for heating cut-out
Circuit Setting range Factory setting
I 10 ... 30 °C 18 °C
Set the outdoor temperature limit at which you
want the heating system to stop.
The valve closes and after about 3 min. the heating
circulation pump stops.
The min. limitation set in line 2 will be ignored.
18 °C
Temp.
Actual Accumulated
outdoor temp. outdoor temp.
Heating OFF
Time
Heating Heating
This function can save energy by stopping the heating system
when the outdoor temperature gets above a set limit. The heating
system switches ON again when the outdoor temperature and
the accumulated outdoor temperature become lower than the set
limit.
The heating cut-out is only active when the controller mode is
scheduled operation. When the limit value is set to 30, there is no
heating cut-out.
Heating cut-out -
line 1
21
Min. flow
temp.
0
1
1
ON
2
094
2
3
ON
2
ON
Max. flow
temp.
Setting range
2 Flow temperature limits, min. and max.
Circuit Setting range Factory setting
I 10 ... 150 °C min. 10 , max. 90 °C
The mentioned setting range and factory settings may vary from
the settings on your ECL Card.
The left end of the setting range blinks. Adjust the
min. limit of your system temperature.
Choose the max. limit. The right end of the setting
range blinks.
Adjust the max. limit.
Flow temperature limits -
line 2
22