Cascade Controller Option
175ZA678.13
Warning:
Touching the electrical parts may be fatal - even after the equipment has
been disconnected from mains.
6002 - 6005, 200-240: wait at least 4 minutes
6006/8006 - 6062 - 6082, 200-240: wait at least 15 minutes
6002 - 6005, 380-460 V: wait at least 4 minutes
6006/8006 - 6072/8072, 380-460/480 V: wait at least 15 minutes
6102/8102 - 6352/8352, 380-460/480 V: wait at least 20 minutes
6402/8452 - 6602/8652, 380-460/480 V: wait at least 40 minutes
6002/8002 - 6006/8006, 525-600 V: wait at least 4 minutes
6008/8008 - 6027/8027, 525-600 V: wait at least 15 minutes
6032/8032 - 6072/8072, 525-600 V: wait at least 30 minutes
6102/8052 - 6402/8402, 525-600/690 V: wait at least 20 minutes
6502-8502 - 6652/8652, 525-600/690 V: wait at least 40 minutes