VLT® 8000 AQUA
Installation
■ Control card
All terminals for the control cables are located
under the protective cover of the AFD.
The protective cover (see drawing below) can be
removed by means of a pointed object (except
IP54/NEMA 12 units) - a screwdriver or similar.
■ Electrical installation, control cables
Torque: 0.5 Nm (5 in-lbs)
Screw size: M3.
Generally speaking, control cables must be shielded/
armored and the shield must be connected by
means of a cable clamp at both ends
to the metal
cabinet of the unit (see Earthing/Grounding of
shielded (armoured control cables).
Normally, the shield must also be connected to the
body of the controlling unit (follow the instructions for
installation given for the unit in question).
If very long control cables are used, 50/60 Hz
ground loops may occur that will disturb the
whole system. This problem can be solved by
connecting one end of the shield to ground via a
100nF capacitor (keeping leads short).
■ Electrical installation, control cables
Torque: 0.5 Nm/5 in-lbs
Screw size: M3
See Earthing/Grounding of shielded (armoured control
cables for correct termination of control cables.
No. Function
04, 05 Relay output 2 can be used for
indicating status and warnings.
12, 13 Voltage supply to digital inputs. For
the 24 V DC to be used for digital
inputs, switch 4 on the control card
must be closed, position "on".
16-33 Digital inputs. See parameters
300-307 Digital inputs.
20 Common for digital inputs.
39 Common for analog/digital outputs.
See Examples of connection.
42, 45 Analog/digital outputs for indicating
frequency, reference, current and
torque. See parameters 319-322
Analoge/digital outputs.
50 Supply voltage to potentiometer and
thermistor 10 V DC.
53, 54 Analog voltage input, 0 - 10 V DC.
55 Common for analog inputs.
60 Analog current input 0/4-20 mA. See
parameters 314-316 Terminal 60.
MG.80.A6.22 - VLT is a registered Danfoss trademark
73