Danfoss VLT 8000 AQUA Instructions d'exploitation Page 9

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 210
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 8
VLT
®
8000 AQUA
Introduction
The voltage of the frequency converter
is dangerous whenever the equipment
is connected to mains. Incorrect
installation of the motor or the frequency converter
may cause damage to the equipment, serious
personal injury or death.
Consequently, the instructions in this manual,
as well as national and local rules and safety
regulations, must be complied with.
Safety regulations
1. The frequency converter must be disconnected
from the mains if repair work is to be carried out.
Check that the mains supply has been disconnected
and that the necessary time has passed before
removing motor and mains plugs.
2. The [OFF/STOP] key on the control panel of
the frequency converter does not disconnect
the equipment from mains and is thus
not to
be used as a safety switch.
3. Correct protective earthing/grounding of the
equipment must be established, the user must be
protected against supply voltage, and the motor
must be protected against overload in accordance
with the National Electrical Code and local codes.
4. The earth leakage currents are higher than 3.5mA.
5. Protection against motor overload is n
ot included in
the factory setting. If this function is required, set
parameter 117, Motor thermal protection,todata
value ETR trip or data value ETR warning.
N
ote: The function is initialised at 1.0 x rated motor
current and rated motor frequency (see parameter
117, Motor thermal protection).InUL/cUL
applications ETR provides Class 20, over-load
protection in accordance with the NEC
®
.
6. Do n
ot remove the plugs for the motor and
mains supply while the frequency converter is
connected to mains. Check that the mains supply
has been disconnected and that the necessary time
has passed before removing motor and mains plugs.
7. Please note that the frequency converter has more
voltage inputs than L1, L2, L3 when the DC-bus
terminals or AUX 24 V option are used.
Check that a
ll voltage inputs have been
disconnected and that the necessary time has
passed before repair work is commenced.
Warning against unintended start
1. The motor can be brought to a stop by means
of digital commands, bus commands, references
or a local stop, while the frequency converter
is connected to mains. If personal safety
considerations make it necessary to ensure
that no unintended start occurs, t
hese stop
functions are not sufficient.
2. While parameters are being changed, the motor
may start. Consequently, t
he stop key [OFF/
STOP] must always be activated, following
which data can be modified.
3. A stopped motor may start if a fault occurs in
the electronics of the frequency converter, or
if a temporary overload or a fault in the supply
mains or the motor connection ceases.
176FA159.15
Warning:
Touching the electrical parts may be fatal - even after the equipment has
been disconnected from line.
VLT 8006-8062, 200-240 V: wait at least 15 minutes
VLT 8006-8072, 380-480 V: wait at least 15 minutes
VLT 8102-8352, 380-480 V: wait at least 20 minutes
VLT 8452-8652, 380-480 V: wait at least 40 minutes
VLT 8002-8006, 525-600 V: wait at least 4 minutes
VLT 8008-8027, 525-600 V: wait at least 15 minutes
VLT 8032-8072, 525-600 V: wait at least 30 minutes
VLT 8052-8402, 525-690 V: wait at least 20 minutes
VLT 8502-8652, 525-690 V: wait at least 30 minutes
MG.83.A2.02 - VLT is a registered Danfoss trademark
7
Vue de la page 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 209 210

Commentaires sur ces manuels

Pas de commentaire