VLT
®
5000 FLUX
Safety
How to use this manual
This manual provides you with the information necessary
to install, start-up and operate the frequency converter.
We recommend you to read this manual carefully.
When using a cross reference in text please
see contents.
You may also visit Danfoss Drives homepage:
www.danfoss.com/drives
Software version
175ZA735.15
VLT 5000 FLUX
Operating Instructions
Software version: 5.5x
These Operating Instructions can be used for VLT 5000 FLUX
frequency converters with software version 5.5x.
The software version number can be seen from parameter 624.
175ZA901.11
Warning:
Touching the electrical parts may be fatal - even after the equipment
has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected,
such as external 24 V DC, load-sharing (linkage of DC intermediate
circuit), as well as the motor connection for kinetic back-up.
Using VLT 5001-5006, 200-240 V: wait at least 4 minutes
Using VLT 5008-5052, 200-240 V: wait at least 15 minutes
Using VLT 5001-5006, 380-500 V: wait at least 4 minutes
Using VLT 5008-5062, 380-500 V: wait at least 15 minutes
Using VLT 5072-5302, 380-500 V: wait at least 20 minutes
Using VLT 5352-5502, 380-500 V: wait at least 40 minutes