VLT 5000/5000 FLUX SyncPos Quick-Setup
MG.10.Q1.5B VLT is a registered Danfoss trade mark16
... the tolerated position error is exceeded
If the test run is constantly interrupted with the
message position error set the parameter for
the
TT
TT
T
olerated position errorolerated position error
olerated position errorolerated position error
olerated position error POSERR (15)
within the tolerable limits as large as possible.
If the position error occur during the acceleration
phase that suggests that the set acceleration
cannot be achieved under the existing load
conditions. Increase the
TT
TT
T
olerated position errorolerated position error
olerated position errorolerated position error
olerated position error
POSERR (15) or determine a maximum
acceleration suitable for the entire system.
If position error do not occur until after the acce-
leration phase and they can be delayed but not
eliminated by increasing the
TT
TT
T
olerated positionolerated position
olerated positionolerated position
olerated position
errorerror
errorerror
error
,,
,,
, this suggests that the maximum velocity
(rpm) chosen is too high. Determine a maximum
velocity suitable for the entire system.
.. the maximum acceleration is not achieved
In general, the technical data for a drive are only va-
lid for a freely rotating axle end. If the drive is carry-
ing a load the maximum acceleration is reduced.
The theoretical maximum acceleration will also
not be achieved if, for example, the PID controller
output is too small or the VLT/motor is not sized
correctly and therefore does not provide enough
energy for peak consumption during acceleration.
10 steps to optimise the PID loop