Feedback to
Network
The VLT LonWorks option provides 22 output
variables to the network containing important
drive and motor feedback data. Feedback data
is sent when there is a change in value. The
VLT LonWorks option will only transmit bound
network variables. Since some data changes
continuously, the transmission rate of those
variables is limited.
Min send time
specifies
the minimum time between transmissions of
variables.
The Drive Output 1 will have a maximum time
between transmission set by the
Max send
time.
This function acts as a transmit heartbeat
and allows a controller node to determine the
health of the controller/VLT connection. The
Max
send time
function is disabled when the
configuration network variable nciMaxsendT is
not configured or is set to “0.
Network Variable Outputs from VLT
Function SNVT type Variable Name Units Max Min
Drive status SNVT_state nvoDrvStatus 16 Boolean NA NA
Drive output 1 SNVT_lev_percent nvoOutputPcnt 0.005% 163.835
163.840
Current
1)
SNVT_amp nvoDrvCurnt 0.1 amps 3276.7 0
Energy SNVT_elec_kwh nvoDrvEnrg 1 kWh 65,535 0
Power
1)
SNVT_power_kilo nvoDrvPwr 0.1 kW 6553.5 0
Statusword SNVT_state nvoStatusWord 16 Boolean NA NA
Output voltage SNVT_volt nvoVoltage 0.1 V 3276.7 –3276.8
Digital input SNVT_state nvoDigitlInput 16 Boolean NA NA
Alarm SNVT_state nvoAlarmWord 16 Boolean NA NA
Warning 1 SNVT_state nvoWarning1 16 Boolean NA NA
Warning 2 SNVT_state nvoWarning2 16 Boolean NA NA
DC voltage SNVT_voltage nvoDCVolt 0.1 V 3276.7 0
Motor therm. Status SNVT_lev_cont nvoTempMtr 0.5 % 100 0
Inverter therm. Status SNVT_lev_cont nvoTempInvrtr 0.5 % 100 0
Analog input SNVT_volt nvoAnalog1 0.1 V 10 0
Ter m. 53
Analog input SNVT_volt nvoAnalog2 0.1 V 10 0
Ter m. 54
Analog input SNVT_amp_mil nvoAnalog3 0,1 mA 20 0
Ter m. 60
Running hours
1)
SNVT_time_hour nvoDrvRunHours 1 Hour 65534 0
Feedback SNVT_lev_percent nvoFeedback 0.01% 100.000 0
Frequency SNVT_freq_hz nvoOutputHz 0.1 Hz 6553.5 0
Drive speed
1)
SNVT_lev_percent nvoDrvSpeed 0.01% 100 0
Output voltage
1)
SNVT_volt nvoDrvVolt 0.1 V 3276.7 0
VLT 5000 parameters are shown in parenthesis, where applicable.
1)
Part of the LonMark Functional Profile for
Variable Speed Drive 6010 version 1.1