Danfoss FC 100 Series Instructions d'exploitation Page 15

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 66
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 14
4.1.8 LED Behaviour
MS: Service LED (red)
Situation LED Description
Configured state (Nornal operation) ½ sec. ON, then continously OFF The node is configures and running nor-
mally
Non configures state Flashing ½ Hz Node is not configures but has an appli-
cation. Proceed with loading node.
Applicationlessstate 1 sec. ON, 2 sec. OFF, then continuosly
ON
Node has no application, the LonWorks
option needs replacing or reprogram-
ming
Watchdog resets Short flash about each 3 sec. Indicates problem with application. The
LonWorks option needs replacing
Faulty hardware Steady ON or OFF The LonWorks option needs replacing
NS: Status LED (green)
Situation LED Description
Node configured Steady ON The node is configures and running
normally
Wink sevice Flashing ½ Hz for 20 sec. Wink service activated in order to
identify node.
VLT® FC 100 LonWorks 4 How to install
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
15