Danfoss FC 100 Series Instructions d'exploitation Page 20

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 66
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 19
5.1.3 FC VSD Profile
The FC VSD Profile describes all Danfoss VLT specific network variables.
Input variables
Variable Function Variable Name SNVT type Profile FC 100 par.
Start/Stop nviStartStop SNVT_switch FC VSD CTW/reference
Control word nviControlword SNVT_state FC VSD CTW
Reset fault nviResetFaut SNVT_switch FC VSD CTW
Reference [%] nviRefPcnt SNVT_lev_percent FC VSD Reference
Reference [Hz] nviRefHz SNVT_freq_hz FC VSD Reference
CL Setpoint 1 nviSetpoint1 SNVT_lev_percent FC VSD 20-21
CL Setpoint 2 nviSetpoint2 SNVT_lev_percent FC VSD 20-22
CL Setpoint 3 nviSetpoint3 SNVT_lev_percent FC VSD 20-23
Bus feedback 1 nviFeedback1 SNVT_lev_percent FC VSD 8-94
Bus feedback 2 nviFeedback2 SNVT_lev_percent FC VSD 8-95
Bus feedback 3 nviFeedback3 SNVT_lev_percent FC VSD 8-96
Digital/relay outputs nviDigiOutput SNVT_state_64 FC VSD 5-90
Analog output (42) nviAnOut1 SNVT_lev_percent FC VSD 6-53
Analog output (X30/8) nvi101AnOut1 SNVT_lev_percent FC VSD 6-63
Analog output (X42/7) nvi109AnOut1 SNVT_lev_percent FC VSD 26-43
Analog output (X42/9) nvi109AnOut2 SNVT_lev_percent FC VSD 26-53
Analog output (X42/11) nvi109AnOut3 SNVT_lev_percent FC VSD 26-63
Setting of RTC nviTimeStamp SNVT_time_stamp FC VSD 0-70
ECB option Mode nviECBMode SNVT_state FC VSD 31-00
ECB By-pass activation nviECBActivation SNVT_switch FC VSD 31-19
Parameter access command nviParamRequest UNVT_param_request FC VSD -
5 Configuration of the system VLT® FC 100 LonWorks
20
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
5
Vue de la page 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 65 66