Danfoss FC 100 Series Instructions d'exploitation Page 52

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 66
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 51
[1] Bus
[2] Logic AND
[3] * Logic OR
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via the fieldbus.
[0] Digital input
[1] Bus Activates Start command via the serial communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-53 Start Select
Option: Function:
Select control of the frequency converter start function via the terminals (digital input) and/or via
the fieldbus.
[0] Digital input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-54 Reversing Select
Option: Function:
Select control of the frequency converter reverse function via the terminals (digital input) and/or
via the fieldbus.
[0] * Digital input Activates Reverse command via a digital input.
[1] Bus Activates Reverse command via the serial communication port or fieldbus option.
[2] Logic AND Activates Reverse command via the fieldbus/serial communication port, AND additionally via one of
the digital inputs.
[3] Logic OR Activates Reverse command via the fieldbus/serial communication port OR via one of the digital
inputs.
8 Parameters VLT® FC 100 LonWorks
52
MG.11.E2.02 - VLT
®