3. How to Configure the System
3.1. Configure the DeviceNet Network
All DeviceNet stations that are connected to
the same bus network must have a unique
station address. The DeviceNet address of the
frequency converter can be selected via:
- Hardware switches (default 63)
- Parameter 10-02
MAC ID
(default
63)
- Class code 0X03, Instance 1, Attrib-
ute 1
3.1.1. Setting the DeviceNet Address using the Hardware Switches
Setting the DeviceNet Address using the Hardware Switches: Using the hardware switches it is
possible to select an address range from 0-63 (factory setting 63) according to the table below:
Switch
8 7 6 5 4 3 2 1
Address value - - +32 +16 +8 +4 +2 +1
Ex. address 5 - - OFF OFF OFF ON OFF ON
Ex. address 20 - - OFF ON OFF ON OFF OFF
Ex. address 35 - - ON OFF OFF OFF ON ON
NB!
Switch off the power supply before changing the hardware switches.
The address change will come into effect at the next power-up, and can be read in par. 10-02
MAC ID
.
3.1.2. Setting the DeviceNet Address via Par. 10-02
MAC ID
The address can be set via par. 10-02
MAC ID
if the hardware switches are set to 63 (factory
setting). The address change will come into effect at the next power-up.
3.1.3. Setting the DeviceNet Address with the Object Class Code
0x03, Attribute 1, Instance 1
The address can be set via the DeviceNet object class code 0x03 attribute 1 command if the
hardware switch is set to 63 (factory setting). A new address becomes effective immediately after
the class code 0x03, Instance 1, Attribute 1 command.