Set point curve Q(U)
Reactive power is defined as a function of the grid voltage, either as a percentage of the nomi-
nal plant power or directly in kVAr. Enter the values for the set point curve under:
Q(U) Curve
.
6.6.2.
Relay Configuration
[1] [Plant]
When grid management box is selected as reference value, configure the discrete inputs K1
K4.
Each of the 16 combinations of the four discrete inputs corresponds to a specific plant output
power level (PLA) and a reactive power output:
Illustration 6.15: Relay configuration
Item
Description
K1-K4 active Enable (check) or disable (uncheck) the individual inputs, K1-K4. If the input is
disabled, its state is ignored (considered off).
Power level in % PLA setting. Output power reduction as percentage of the plant nominal AC
power.
Reactive power Reactive power (Q) output in % or kVAr.
Power factor Output power factor (PF).
6.6.3.
Set Point Curves
[1] [Plant]
The TLX CN Pro+ inverter is capable of generating reactive power on basis of predefined set
point curves, either:
Reactive power (Q) as a function of the grid voltage
Power Factor (PF) as a function of the plant output power
The set point curves are defined by values and displayed as a graphical curve.
6. Setup
40 L00410583-01_02