Danfoss DLX 4.6 Guide d'installation Page 20

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 48
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 19
20 Installation Guide DLX series L00410622-01
2.4.4.1. Connection Procedures
Figure 2.4.10: Connection area with AC terminals
1. AC terminal block:
GND: Ground terminal
N: Neutral terminal (TN/TT) or Phase terminal (IT)
L: Phase terminal
2. Cable gland
Use copper wire with a maximum cross-section area of 16 mm
2
/ 6 AWG. Ensure
compliance with the relevant national electrical regulations!
The AC conductor resistance should be minimized.
Unscrew the cable gland locknut.
Guide the AC cable through the opening, and connect the conductors to the
corresponding terminals in the connection area:
Phase conductor (L1 or L2 or L3) to L
Neutral conductor (TN/TT) or Phase conductor (IT) to N
Grounded conductor to GND
Tightening torque of the terminal screws is 1.5 Nm
Double check if the connection is correctly carried out.
Hand-tighten the gland locknuts to seal the cable gland.
Vue de la page 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 47 48

Commentaires sur ces manuels

Pas de commentaire