5 How to Install
Enclosure frame size
Mains voltage
H1 H2 H3 H4 H5 H6 H7 H8
T2 (200-
240V AC)
0.25-1,5kW/
0.33-2Hp
2.2kW/
3Hp
3.7kW/
5Hp
5.5-7,5kW/
7.5-10Hp
11kW/
15Hp
T4 (380-
480V AC)
0.37-1.5kW/
0.5-2Hp
2.2-4kW/
3-5.4Hp
5.5-7.5kW/
7.5-10Hp
11-15kW/
15-20Hp
18.5-22/
25-30Hp
30-45kW/
40-60Hp
55-75kW/
73-100Hp
90kW/
125Hp
IP IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20
Height
Enclosure A
195mm/7.7
inch 227/8.4 inch 255mm/10 inch 296mm/11.7 inch 334mm/13.1 inch 518mm/20.4 inch 550mm/21.7 inch
660mm/26
inch
Heigth incl.
decoupling plate
273mm/
10.7 inch
303/
11.9 inch
329mm/
13inch
359mm/
14.1 inch
402mm/
15.8 inch
595mm/
23.4inch
635mm/
25inch(45kW)
630mm/
24.8 inch
690mm/
27.2 inch (75kW)
800mm/
31.5 inch
Between mounting
holes a
183mm/
7.2inch
212/
8.3 inch
240mm/
9.4 inch
275mm/
10.8 inch
314mm/
12.4 inch
495mm/
19.5 inch
521mm/
20.5 inch
631mm/
24.8 inch
Width B
75mm/
3 inch
90/
3.5 inch
100mm/
3.9 inch
135mm/
5.3 inch
150mm/
5.9 inch
239mm/
31.5 inch
313mm/
12.3 inch
375mm/
14.8 inch
Between mounting
holes b
56mm/
2.2 inch
65/
2.6 inch
74mm/
2.9 inch
105mm/
4.1 inch
120mm/
4.7 inch
200mm/
7.9 inch
270mm/
10.6 inch
330mm/
13 inch
Depth C
168mm/
6.6 inch
190mm/
7.5 inch
206mm/
8.1 inch
241mm/
9.5 inch
255mm/
10 inch
242mm/
9.5 inch
335mm/
13.2 inch
335mm/
13.2 inch
Mounting holes d
9mm/
0.35 inch
11mm/
0.43 inch
11mm/
0.43 inch
12.6mm/
0.50 inch
12.6mm/
0.50 inch - - -
e
4.5mm/0.18
inch
5.5mm/0.22
inch 5.5mm/0.22 inch 7mm/0.28 inch 7mm/0.28 inch 8.5mm 8.5mm 8.5mm
f
5.3mm/
0.21 inch
7.4mm/
0.29 inch
8.1mm/
0.32 inch
8.4mm/
0.33 inch
8.5mm/
0.33 inch 15mm 17mm 17mm
Maximum weight 2.1kg 3.4kg 4.5kg 7.9kg 9.5kg 24.5kg 36kg 51kg
Shipping dimensions
Height
255mm/
10.0inch
300mm/
11.8inch
330mm/
13.0inch
380mm/
15.0inch
420mm/
16.5inch
460mm/
18.1 inch
540mm/
21.3 inch
490mm/
19.3 inch
Width
154mm/
6.1inch
170mm/
6.7inch
188mm/
7.4inch
250mm/
9.8inch
290mm/
11.4inch
850mm/
33.5 inch
850mm/
33.5 inch
950mm/
37.4 inch
Depth
235mm/9.3
inch
260mm/10.2
inch 282mm/11.1 inch 375mm/14.8 inch 375mm/14.8inch 370mm/14.6 inch 410mm/16.1 inch
490mm/19.3
inch
Table 5.1 Mechanical Front Views