Danfoss FC 100 Series Spécifications Page 85

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 93
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 84
8.1.3 Mains Supply 3 x 380-480VAC
Frequency converter P22K P30K P37K P45K P55K P75K P90K
Typical shaft output (kW) 22.0 30.0 37.0 45.0 55.0 75.0 90.0
Typical shaft output (hp) 30.0 40.0 50.0 60.0 70.0 100.0 125.0
IP54 frame I6 I6 I6 I7 I7 I8 I8
Max. cable size in terminals (mains, motor) [mm
2
/AWG]
35/2 35/2 35/2 50/1 50/1 95/(3/0) 120/(4/0)
Output current
RELAY 2
130BB632.10
40°C ambient temperature
Continuous
(3x380-440V)[A]
44.0 61.0 73.0 90.0 106.0 147.0 177.0
Intermittent
(3x380-440V)[A]
48.4 67.1 80.3 99.0 116.6 161.7 194.7
Continuous
(3x440-480V)[A]
40.0 52.0 65.0 80.0 105.0 130.0 160.0
Intermittent
(3x440-480V)[A]
44.0 57.2 71.5 88.0 115.5 143.0 176.0
Max. input current
RELAY 2
130BB633.10
Continuous
(3x380-440V)[A]
41.8 57.0 70.3 84.2 102.9 140.3 165.6
Intermittent
(3x380-440V)[A]
46.0 62.7 77.4 92.6 113.1 154.3 182.2
Continuous
(3x440-480V)[A]
36.0 49.2 60.6 72.5 88.6 120.9 142.7
Intermittent
(3x440-480V)[A]
39.6 54.1 66.7 79.8 97.5 132.9 157.0
Max. mains fuses
Frequency converter P22K P30K P37K P45K P55K P75K P90K
Estimated power loss [W], Best case/typical
1)
496 734 705 927 1075 1425 1469
Weight enclosure IP54kg] 27 27 27 45 45 65 65
Efficiency [%], Best case/Typical 1 98.0 97.8 98.3 98.3 98.3 98.3 98.5
Output current
50°C ambient temperature
Continuous
(3x380-440V) [A]
35.2 48.8 58.4 63.0 74.2 102.9 123.9
Intermittent
(3x380-440V) [A]
38.7 53.9 64.2 69.3 81.6 113.2 136.3
Continuous
(3x440-480V) [A]
32.0 41.6 52.0 56.0 73.5 91.0 112.0
Intermittent
(3x440-480V) [A]
35.2 45.8 57.2 61.6 80.9 100.1 123.2
General Specifications and ... VLT HVAC Basic Drive Design Guide
84 MG.18.C2.02 - VLT
®
is a registered Danfoss trademark
88
Vue de la page 84
1 2 ... 80 81 82 83 84 85 86 87 88 89 90 91 92 93