User Guide DLX Series L00410623-1 29
4.3.4.6. Jumper Position for the System Grounding Setup
The jumper above the - NEG terminal in the customer connection area monitors the
arrangement of the DC connection according to the system grounding setup. When
delivered, the jumper is positioned in an ungrounded string configuration as standard.
Depending on the grounding requirements from the module manufacturer the jumper
must be pulled up and positioned correctly to match the required grounding of the PV
strings.
In case of a mismatch in grounding setup the following message will appear in the display
“Fuse fault”. Refer to 7.2. Table of Events.
Table 4.1: Position for the jumper monitoring the grounding setup
Connection Area Topview System
1. Jumper for the grounding setup
Ungrounded PV String Configuration:
There is no connection between the pins.
Positive grounded PV String
Configuration: The jumper connects the two
leftmost pins.
Negative grounded PV String
Configuration: The jumper connects the two
rightmost pins.
4.3.5. AC Connections (Grid)
The AC connection includes wiring from the AC distribution panel through one or more
circuit breakers to the AC terminal block of the inverter.
Verify that the AC grid specifications are compatible with the inverter characteristics
before connecting the inverter to the AC grid:
• Single phase/Split phase
• Voltage range (184 – 276 V)
• Frequency range (50 Hz ±5 Hz)
CAUTION
The AC output / Neutral of the inverter is not bonded to ground.
DANGER
Turn OFF the AC circuit breaker(s) before connecting the inverter to the utility grid
to prevent electrocution.