Danfoss DLX 4.6 Guide de l'utilisateur Page 81

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 86
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 80
User Guide DLX Series L00410623-1 81
Figure 8.2.5: Varistors on the DC side
8.2.9.2. AC Side
No alarms are raised regarding the condition of the varistors on the AC side. Therefore,
they need to be checked regularly (at least once per year) or after lightning strikes.
Replace the damaged varistor with DLX Varistor Kit ordered from Danfoss, part number
139B0570.
The three varistors on the AC side are located in the right side of the connection area
above the AC terminal area.
Note the orientation of the varistors if they need to be replaced.
Figure 8.2.6: Varistors on the AC side
Check Varistor
Measure the ohms between the terminal and the bent pin on each varistor as per the
below diagrams: