User Guide DLX Series L00410623-1 61
Grid Connect
Grid Connect displays limits related to reconnection of the inverter according to the
selected grid standard.
Name
Name of grid connect standard
V
AC
min connect
Minimum voltage for reconnection to grid
V
AC
max connect
Maximum voltage for reconnection to grid
f
AC
min connect
Minimum frequency for reconnection to grid
f
AC
max connect
Maximum frequency for reconnection to grid
6.2.4.6. Change the Country Settings
From the Main Menu: Select Setup >General Grid Setup > Grid Code.
Enter - Confirm.
After 5 hours of feeding-in power to the grid the Installer password must be used to
change the grid code settings. The Installer password is available for installers and grid
operators only by contacting Danfoss.
The question “Change grid code?” appears in the display.
OK – Continue
Cancel – The operation is cancelled
Up or Down Select the respective country
Enter Confirm
Left – Back
Right – Next
Enter – Confirm
After the country settings are changed, the screen will return to the Grid Setup screen,
showing the new grid settings.