Connecting the inverters
Ingeteam
66 of 268 Solar-Log
1000/500/200
Installation
Procedure
1 Open the inverter as described in the inverter instructions.
2 Pull the free wires through the wire opening in the inverter.
3 If you have made the cable connection yourself connect the wires as
shown in the following diagram:
Solar-Log™ terminal block connector
4 If only one inverter is to be connected it must be terminated:
Insert jumper JP3 into the RS485 card.
5 Close the inverter if no other inverters are to be connected.
6 Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connecting the inverters to each other (Solar-Log
500
, Solar-Log
1000
)
Connect using a 3 wire, shielded data cable.
Where to connect: Terminal strip inside the inverter (on the retrofitted
RS485 interface)
Procedure
1 Open the inverter as described in the inverter instructions.
2 Connect terminals “Pin 1-RS485-A (+)”, “Pin 6-GND” and “Pin 2-RS485-B
(-)” of inverter 1 to the corresponding terminals on inverter 2.
3 Connect the other inverters to each other in the same way.
4 Terminate in the last inverter:
Insert jumper JP3 into the RS485 card.
5 Close inverters.
Allocating communication address
Recommendation: Continuous numbering starting with 1.
Setting: Using the inverter operating display
Procedure: As set out in the inverter's instructions